Generator Technical Characteristic Testing

  • Generator Technical Characteristic Testing related photo 1
  • Generator Technical Characteristic Testing related photo 2
  • Generator Technical Characteristic Testing related photo 3
  • Generator Technical Characteristic Testing related photo 4
  • Performance of on-site testing, simulation, and analysis to derive generator facility model parameters, which are essential for reliable power system operation
  • Test Cycle (Standards for Maintaining Power System Reliability and Power Quality)
Generator Technical Characteristic Testing test cycle standards by class
Div. Thermal Power Combined-Cycle Power Hydropower
Class 1 500MVA↑ 400MVA↑ 200MVA↑
Class 2 500MVA↓ 400MVA↓ 200MVA↓
  • Test Cycle (Standards for Maintaining Power System Reliability and Power Quality)
    • When a generator is newly installed, expanded, or modified
    • When modules of the exciter, governor, or power system stabilizer are replaced
    • When neither Item 1 nor Item 2 has occurred within the past 10 years

Diagnosis Service

Site Test

  • No-load saturation curve test
  • No-load AVR step response test
  • PSS performance test, 100% MW
  • Maximum and minimum reactive power limit test, 100% MW
  • V-curve test, 100%, 75%, 50%, and 25% MW
  • Governor step response test, 75% MW
  • Load rejection test, 20% MW and 10 Mvar

Simulation & parameter derivation

  • Generator (GENROU, GENSAE models, etc.)
  • Governor (IEEEG1, GGOV1, PIDGOV models, etc.)
  • Exciter (ESST4B, EXST1, ST6B, IEEEX2 models, etc.)
  • Power system stabilizer (IEEEST1, PSS2A, PSS2B, etc.)